Genset Controller >> Synchronising and Load Sharing

Trans-MAINS

Information

Automatic Transfer & Load Share Unit With Mains

Load sharing with genset (up to 32 gensets) Busbar voltages and frequency measurements Bus failure detection Peak lopping (mains or genset) Power export to mains Mains de-coupling protection with R.O.C.O.F and vector shift methods Volts, frequency and phase matching Synchroscope display Logic Controller functionality for PLC
 

Specifications : 

Communication interface USB programming and communication port, CanOpen, Ethernet, RS485.
Inputs 13x Configurable digital
Outputs Configurable 9x Transistors, GBR outputs
Current Measurement 3 phases CT inputs for Load Current, 1x CT input for Earth Current
Voltage Measurement 3 phases for Alternator
Power Factor Measurement For 3 phases

 

Case : 

Dimensions 276mm x 189mm x 45mm
Panel Cut-Out 223mm x 162mm
Protection IP65 at front side
Weight Approximately 0,82Kg

 

Ratings : 

DC Battery Supply range 8 to 32Vdc, max.operating current is 860mA
CT Secondary 5A
Sender Measurement 0 to 1300 ohm, accuracy: 1%FS, resolution: 1 ohm
Cabin. Temp. Measuremet -50 to +100 ºC, accuracy: 1 % FS, resolution: 1 ºC.
Operating / Storage Temp. -20°C to +70°C / -30°C to +80°C